Phase-Sequence Network
CircuitSim
·
Created Oct 3, 2026
·
Updated Oct 3, 2026
Details
Components
3
Schematic
Yes
Simulation
Transient analysis
Copies
Not copied yet
About this circuit
Use a resistor-capacitor network to distinguish the two rotation orders of a balanced three-phase supply.
Circuit notes
Phase-Sequence Network
Use a resistor-capacitor network to distinguish the two rotation orders of a balanced three-phase supply.
VA, VB and VC form a balanced three-phase set: 10 V peak at 50 Hz, with phases 0°, −120° and +120°. R1 = 1 kΩ connects phase A to the sense node; C1 = 3.18309886 µF connects phase B to that node. RL = 1 kΩ connects the sense node to phase C.
The resistor and capacitor weight two phases differently. Reversing the phase order changes whether their contributions reinforce or partially cancel relative to phase C. For these values, Vsense is about 14.964 V peak for the saved A–B–C order and 4.010 V peak when B and C are swapped.
Read the chart. Vab is the line-to-line voltage measured with reference marker B. Vsense is measured relative to reference marker C. Isense flows through RL toward phase C. The first cycle contains the capacitor startup transient; compare the later cycles. The reference markers are measurement points, not extra ground connections.
Try it. Change VB’s Phase to +120° and VC’s Phase to −120°. Run again and compare the sense amplitude. Restore VB to −120° and VC to +120°. Keep all three frequencies and amplitudes equal.
Model limits. This is a passive sequence-sensitive network, not a complete protective relay. A practical detector also needs thresholding, filtering and appropriate voltage isolation.
Components used
Components used
3 components
Try this circuit yourself
Free to get started. No download — runs in your browser with a full SPICE engine.