Long Distance Power Transmission
CircuitSim
·
Created Oct 3, 2026
·
Updated Oct 3, 2026
Details
Components
3
Schematic
Yes
Simulation
Transient analysis
Copies
Not copied yet
About this circuit
Reduce line current and resistive power loss by stepping voltage up for transmission and down at the load.
Circuit notes
Long Distance Power Transmission
Reduce line current and resistive power loss by stepping voltage up for transmission and down at the load.
A 10 V peak, 1 kHz source drives a 1:10 step-up transformer. RLINE = 20 Ω represents the total series resistance of the transmission path. A 10:1 step-down transformer feeds RLOAD = 100 Ω.
The load receives about 9.980 V peak and 0.498 W average. For the same delivered voltage and load power, higher transmission voltage permits lower line current; resistive line loss falls with the square of that current.
Try it. Change both transformers’ Secondary coil turns to 10, leaving Primary coil turns at 10. Both then become 1:1. The load falls to 8.333 V peak and line loss rises to 69.44 mW. Restore T1 secondary turns to 100 and T2 secondary turns to 1. Those values reproduce the 1:10 and 10:1 ratios.
Read the chart. Vin is green and Vload red. Iline is blue; Iload is purple. The 20 Ω resistor represents both conductors’ combined loss, not just one conductor.
Model limits. This scaled example uses ideal transformers and a resistive line. It omits line inductance, capacitance, insulation constraints and transformer losses. Grounds are numerical references, not a detailed utility grounding system.